Charging Pump Overrun; Frost Protection For The D.h.w - Siemens RVD110 Basic Documentation

District heating and domestic hot water controllers
Table of Contents

Advertisement

Notes
Caution
48/94
Siemens Building Technologies
HVAC Products
• With pump heating circuits (plant types no. 2 through 7), it can occur that too hot
water reaches the heating circuit. Caution should be exercised particularly in the
case of underfloor heating systems!
A mixing heating circuit (plant type no. 8), by contrast, can lower its flow temperature
through mixing
• With plant types no. 4 through 6, the space heating circuit and the d.h.w. circuit re-
ceive their heat from separate heat exchangers. Shifting priority acts like parallel pri-
ority; the demand (d.h.w. or maximum selection) is not of any relevance.
Nevertheless, the setting can be made
• No priority can be selected with plant type no. 3. The diverting valve always ensures
absolute priority
• If, during charging pump overrun, the heating circuit calls for heat, the heating circuit
pump will be activated, independent of the selected priority

14.3.5 Charging pump overrun

To avoid the cumulation of heat, charging pump overrun can be selected, depending on
the type of plant. The required overrun time is to be entered on operating line 107. Set-
ting 0 deactivates the function.
• Plant types no. 2, 6 and 8: Each time d.h.w. heating is terminated, charging pump
Q3 overruns for the period of time entered
• Plant type no. 3: Each time d.h.w. heating is terminated, diverting valve Y7 maintains
its position for the period of time entered (in that respect, the diverting valve is
treated like the charging pump)
• Plant type no. 6: Each time d.h.w. is drawn, charging pump Q3 overruns for the pe-
riod of time entered
• Plant type no. 7: Each time d.h.w. heating is terminated, both charging pump Q3
(primary circuit) and charging pump Q7 (secondary circuit) overrun for the period of
time entered.
With this type of plant, the overrun time of charging pump Q7 can be entered sepa-
rately (operating line 108). It starts only after the overrun time of pump Q3 has
elapsed
With plant types no. 2, 3, 7 and 8, d.h.w. stops its pump overrun when the heating cir-
cuit demands heat from the heat exchanger and the common flow temperature is lower
than the demand.
The overrun function is not affected by the type of priority. Pump overrun can be inter-
rupted by protection against the discharging of d.h.w. or by locking signals initiated by
heat generating equipment or heat consumers.

14.3.6 Frost protection for the d.h.w.

The d.h.w. storage tank is protected against frost. Frost protection for d.h.w. is auto-
matically activated when the d.h.w. temperature (sensor B3 or B71) drops below 5 °C.
The charging pump (diverting valve with plant type no. 3) will be activated and a d.h.w.
temperature of at least 5 °C is maintained. This frost protection is used with both d.h.w.
heating ON (operating mode button
No frost protection for the d.h.w. is possible with plant types no. 4 and 5.
If, with plant types no. 6 and 7, a d.h.w. thermostat is used in place of a sensor, no frost
protection for the d.h.w. is possible.
Basic Documentation RVD110, RVD130
14 Function block D.h.w. heating
lit) and d.h.w. heating OFF.
CE1P2381E
27.05.2004