Code
Error type
11
Numeric
12
Counting range
14
Inconsistent data
15
Parameter error
32
Counter preset
33
Transfer range no./transfer preset no.
34
Beginning word no.
35
Data area
36
Number of transfers
Appendix A
Error Codes
Data is not BCD or data is 0.
Data is less than –8,388,608 or greater than
8,388,607. (Circular mode: data is less than 0 or greater than 65,535.)
The mode setting on the front panel and the operating mode set in DM
area are inconsistent, or upper and lower settings for ranges are
reversed.
Error in parameters other than those covered under codes 11, 12, and
14, above.
The counter preset number is not between 00 and 19.
The range number for TRANSFER DATA is not between 00 and 15
transfer preset no. or the preset number for TRANSFER DATA is not
between 00 and 19.
The beginning word number for TRANSFER DATA is not acceptable.
The data area number for TRANSFER DATA is not acceptable.
The number of transfers exceeds the specified maximum or is set to 0.