Omron SYSMAC C200H-CT001-V1 Operation Manual page 68

High-speed counter units
Hide thumbs Also See for SYSMAC C200H-CT001-V1:
Table of Contents

Advertisement

Preset Mode
Outputs
54
Word
Bit
n
00
START command (The START command is effective only
when pin 4 on the back-panel DIP switch is turned OFF. If pin
4 is ON, control input IN2 is used to start and stop the
Counter Unit.)
01
TRANSFER DATA command
02
ENABLE OUTPUT command
03
Not used.
04
CHANGE PRESET command
05
READ ERROR command
06
RESET COUNTER command
07
ENABLE FORCED OUTPUT command
08
Output #0 force bit
09
Output #1 force bit
10
Output #2 force bit
11
Output #3 force bit
12
Output #4 force bit
13
Output #5 force bit
14
Output #6 force bit
15
Output #7 force bit
n+1
Not used.
07
04
Preset number, 2 digits, between 00 and 19
15
08
n+2
TRANSFER DATA beginning word number, 4 digits
15
00
n+3
TRANSFER DATA data area, 0 through 4
03
00
Not used. (Set to 0.)
07
04
Number of transfers, 1 through 3
15
08
Section 4-3