INSTALLING INSTRUCTIONS
WARNING:
according to the electrical safety.
The ceiling heater must be grounded in accordance with all national
and local building codes.
All wiring procedures and connections shall be in accordance
with the national and local codes having jurisdiction.
Before installation:
Disconnect the main supply connection.
Supply cables shall be 6 AWG (13.3 mm
The heater must be connected to individual branch circuit protected
by 60Amp circuit breaker only.
Supply cables must be equipped with a dual pole circuit breaker
rating at least 240V 60A/pole as main cutoff switch of power
connection to the heater.
Wiring compartment for accommodating supply cables and pigtail
leads are adequate and measured free space of 2524.67 cm
CAUTION:
drapery, furnishings, and other combustibles at least 3 feet (0.9 m)
from the front of the heater and away from the side and rear.
WARNING:
gasoline or other flammable vapors and liquids in the vicinity of the
heater.
INSTALLATION INSTRUCTION:
1. Keep the unit at least 6 feet(1.8 m in U.S.A)/ 8 feet (2.4 m in
Canada) away from the floor. This minimum distance must be
maintained.
2. Do not install closer than1 foot (or 0.3 m) to any adjacent vertical
surfaces or walls.
3. Keep at least 4.5 inches (11.5cm) from the back wall (with or
All wiring must be installed by a certified electrician
High temperature, risk of fire, keep electrical cords,
To reduce the risk of fire, do not store or use
2
) copper wires.
5
3
.