INSTALLATION INSTRUCTIONS
P15 – D.
P
.
ARAMETER
H
This parameter is used to set the D.H.W maximum user set point.
To enter the parameters menu, follow the previously described
procedure (see paragraph 5.2 'Accessing the parameters menu' -
steps 1-5).
6. Use '
' and '
' buttons (D.H.W temperature setting)
modify the value of the parameter within the prescribed limits
(displayed in Fahrenheit degrees):
113 – 167°F
7. Press mode selection button '
new adjustment operative. The parameter number (P15) will
appear on the display.
8. To exit from the parameters menu, press simultaneously '
'
' buttons.
P16 – P
P
ARAMETER
OST VENTILATION
This parameter is used to set the fan functioning time, after switching
off the burner.
To enter the parameters menu, follow the previously described
procedure (see paragraph 5.2 'Accessing the parameters menu' -
steps 1-5.
6. Use '
' and '
' buttons (D.H.W temperature setting)
modify the value of the parameter within the prescribed limits
(displayed in minutes):
00 - 10
7. Press mode selection button '
new adjustment operative. The parameter number (P16) will
appear on the display.
8. To exit from the parameters menu, press simultaneously '
'
' buttons.
.
W
MAXIMUM SET POINT
' to confirm and to render the
' to confirm and to render the
to
' and
to