INSTALLATION INSTRUCTIONS
P09 – S
P
ARAMETER
This parameter is used to set the gas pressure during the starting up of the
boiler.
To enter the parameters menu, follow the previously described procedure
(see paragraph 5.2 'Accessing the parameters menu' - steps 1-5).
6. Use '
' and '
' buttons (D.H.W temperature setting)
the value of the parameter within the prescribed limits:
00 = minimum mechanical gas pressure set at the gas valve;
99 = maximum allowed pressure, depending on the chimney length and
the type of gas used.
The default value is 50.
7. Press mode selection button '
adjustment operative. The parameter number (P09) will appear on the
display.
8. To exit from the parameters menu, press simultaneously '
buttons.
P10 – D.H.W. P
P
ARAMETER
(Not applicable to instantaneous boilers w/dual circuit exchanger)
This parameter allows to maintain the diverter valve on D.H.W mode for a
time equal to the post-circulation, keeping hot the secondary heat exchanger.
To enter the parameters menu, follow the previously described procedure
(see paragraph 5.2 'Accessing the parameters menu' - steps 1-5).
6. Use '
' and '
' buttons (D.H.W temperature setting)
the value of the parameter:
00 = Off
01 = On
7. Press mode selection button '
adjustment operative. The parameter number (P10) will appear on the
display.
8. To exit from the parameters menu, press simultaneously '
buttons.
11 – LEGIONELLA
P
ARAMETER
(For storage boilers only)
To enter the parameters menu, follow the previously described procedure
(see paragraph 5.2 'Accessing the parameters menu' - steps 1-5).
6. Use '
' and '
' buttons (D.H.W temperature setting)
the value of the parameter:
00 = Off
01= on (default value in storage boilers)
7. Press mode selection button '
adjustment operative. The parameter number (P11) will appear on the
display.
8. To exit from the parameters menu, press simultaneously '
buttons.
ETS THE IGNITION SEQUENCE
' to confirm and to render the new
RIORITY FUNCTION
' to confirm and to render the new
PREVENTION FUNCTION
' to confirm and to render the new
to modify
' and '
'
to modify
' and '
'
to modify
' and '
'
59