24
P07
30
P07
INSTALLATION INSTRUCTIONS
P
P07 - M
ARAMETER
12. Enter the parameters menu and select parameter P07. The pressure
gauge will indicate the gas pressure. If this pressure value is different to
that on the rating plate of the boiler (see paragraph 5.5 'Gas Data'), use
'
' and '
' buttons (D.H.W temperature setting)
value of the parameter. The range of settings is 00 - 80.
13. Press mode selection button '
new adjustment operative. The parameter number (P07) will appear
on the display.
14. Press simultaneously '
the display.
15. Disconnect the manometer from the pressure test port 'B' on the gas
valve and carefully tighten the screw making sure there are no gas
leaks.
BTU
INIMUM
OUTPUT
' to confirm and to render the
' and '
buttons until OFF appears on
to modify the
57