7.2

Details of remote register

7.2.1

Remote register (master module to inverter (FR-A7NC))

Remote register definition
Device No.
Signal
Monitor code1/
RWw0
Monitor code2
RWw1
Set frequency
*1
When Pr. 37 is not equal to "0", this will be machine speed display (1 increments).
*2
When Pr.541 Frequency command sign selection (CC-Link) = "1", the setting value has either + or -. When the setting
value is negative, the command is inversed from starting command.
Setting range: -327.68Hz to 327.67Hz (-327.68 to 327.67) 0.01Hz increments.
For details refer to page 38.
Set the monitor code to be monitored. By setting "1" in RYC after setting, the
specified monitored data is stored in RWr0/RWr1.
Refer to page 66 for monitor code details.
 Specify the set frequency or machine speed. At this time, whether to write to
RAM or EEPROM is decided with the RYD and RYE settings. After setting the set
frequency in this register, set "1" in RYD or RYE to write the frequency. After
writing of frequency is completed, "1" is set in RXD or RXE in response to the
*1, *2
input command.
 The setting range is 0 to 400.00Hz (0.01Hz increments). Write "40000" when
setting 400.00Hz.
DETAILS OF INPUT AND OUTPUT SIGNALS
Description
7
55