9.2
When two or more inverters are connected
The following system configuration shows how the cause of a fault can be checked with the LED status of
the inverter communication option (FR-A7NC) and countermeasures for the fault.
(In this example, assume SW, M/S, and PRM LEDs of the master module are OFF (master module is in
normal operation).)
Power
supply
LED Status
Inverters (FR-A7NC)
Master
Module
Station 1 Station 2 Station 3
RUN
RUN
L.RUN
L.RUN
SD
SD
TIME
RD
RD
LINE
L.ERR
L.ERR
or
RUN
RUN
TIME
L.RUN
L.RUN
LINE
SD
SD
RD
RD
L.ERR
L.ERR
HOW TO CHECK FOR ERROR USING THE LEDS
CPU
Master
module
Station 1
Inverter A
FR-A7NC
RUN
L.RUN
SD
Normal
RD
L.ERR
RUN
L.RUN
Poor contact of the FR-A7NC with the
SD
inverter
RD
L.ERR
Station 2
Inverter B
FR-A7NC
Cause
: ON,
: OFF,
: Flicker, *: Any of ON, flicker or OFF
Station 3
Inverter C
FR-A7NC
Corrective Action
Plug the FR-A7NC securely.
Check the connector.
85