HOW TO CHECK FOR ERROR USING THE LEDS
LED States
Inverters (FR-A7NC)
Master
Module
Station 1 Station 2 Station 3
RUN
RUN
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
L.ERR
TIME
RUN
RUN
LINE
L.RUN
L.RUN
or
SD
SD
TIME
RD
RD
LINE
L.ERR
L.ERR
RUN
RUN
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
L.ERR
88
RUN
Since the L.ERR LED of the FR-A7NC
L.RUN
on station 2 is ON, the FR-A7NC itself
SD
on station 2 is affected by noise.
RD
(L.RUN may go OFF.)
L.ERR
RUN
Since the L.ERR LEDs of the FR-
L.RUN
A7NC on station 2 and later are ON,
SD
the transmission cable between the
RD
inverters of stations 2 and 3 is affected
L.ERR
by noise. (L.RUN may go OFF.)
RUN
L.RUN
Terminating resistor is not selected.
SD
(L.RUN may go OFF.)
RD
L.ERR
: ON,
Cause
Securely connect FG of each
inverter and master module
to ground.
Check that the transmission
cable is connected to SLD.
Also run it as far away as
possible from the power
lines. (100mm or more)
Check that the setting of the
terminating resistor selection
switch is correct.
(refer to page 13)
: OFF, : Flicker, *: Any of ON, flicker or OFF
Corrective Action