Advant Controller AC 31 / Issued: 01.99
Conditions,
Action
Menu item
Abort
Cold start
RUN/STOP switch set to RUN,
power ON
RUN/STOP switch,
RUN
Menu item
Abort
Start
Initialization: digital flags
Absolute identifier:
Symbolic identifier:
Value n of the system constant KW 00.01
n = 0 (default)
n = 1...99
n = 100...229
n = 230...254
n < 0, n > 255
Comments:
The bits M 255,00 to M 255,03 are oscillator variables which always start at 0.
The bits M 255,10 to M 255,14 are reserved for diagnostic tasks.
The bit M 255,15 cannot be saved and is reset to 0 each time the program is started. It is
therefore suitable for recognizing the first program cycle.
Example:
KW 00,01 = 20
Initialized bits:
M 020,00...M 099,15
M 230,00...M 255,15
Backed up bits:
M 000,00...M 019,15
Flags, step chains and historical values
which are initialized (set to 0).
all
In accordance with the values of the system
constants, (see below)
KW 00,01
INIT_M
Digital flag areas which are initialized
(set to 0)
M 000,00...M 099,15
M 230,00...M 255,15
M
n,00...M 099,15
M 230,00...M 255,15
M 230,00...M 255,15
M
n,00...M 255,15
M 255,00...M255,15
5 – 9