Digital Central Extensions Specifications - ABB 07CR41 Operating Manual

Series 40 and 50
Table of Contents

Advertisement

3.5.2

Digital central extensions specifications

Weight
Integrated digital inputs
- Number of inputs
- Isolateds inputs (test voltage)
- Types of inputs
- Input voltage:
nominal value
signal at 0 (IEC 1131-2)
signal at 1 (IEC 1131-2)
- Input current at 24 V d.c.
- Signal delay time
- Cable length:
unshielded
shielded
Integrated outputs
- Number of outputs
- Isolated outputs (test voltage)
- Load current, under/channel:
24 V d.c.
alternate 24 to 230 V a.c.
- Total load current
- Output leakage current
- Leakage voltage
- Minimum load
3
Technical specifications
The digital extension units are powered at 5 V by the basic unit or extensible remote unit to
which they are connected.
Warning: the extensions must not be connected or disconnected under power supply.
XI 16 E1
220 g
16
1500 V a.c.
PNP
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
4 mA
5 ms
300 m
500 m
-
-
-
-
-
-
-
-
XO 08 R1
XC 08 L1
220 g
220 g
-
8 configurable
-
1500 V a.c.
-
PNP
-
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
-
4 mA
-
5 ms
-
300 m
-
500 m
8 relays
8 transistors
1500 Vrms
1500 V a.c.
1 min
1 min
2 A
0.5 A
2 A AC-1
-
0.5 A AC-15
8 x 2 A
8 x 0.5 A
< 200 µA
0.5 V to 500 mA
max.
10 mA at
12 V
12 V d.c.
3 – 16
XK 08 F1
XO 16N1
220 g
220 g
4
-
1500 V a.c.
-
PNP
-
24 V d.c.
-
0 to + 5 V
+ 15 to + 30 V
7 mA
-
5 ms
-
300 m
-
500 m
-
4 relays
16 transistors
1500 Vrms
1500 V a.c.
1 min
1 min
2 A
0.5 A
2 A AC-1
-
0.5 A AC-15
4 x 2 A
16 x 0.5 A
< 200 µA
0.5 V to 500 mA
max.
10 mA at
12 V
12 V d.c.
Advant Controller AC 31 / Issued: 01.99