Technical Specifications Of The Centrally Extensible Remote Units - ABB 07CR41 Operating Manual

Series 40 and 50
Table of Contents

Advertisement

3.4.2 Technical specifications of the centrally extensible remote units

3
Technical specifications
- Weight
Power supply
- Mains voltage:
nominal value
admissible range
- Consumption:
unit alone (typical)
maximum configuration (typical)
- Polarity reversal protection
- Integrated power supply 24 V d.c.
for the inputs:
range of voltage value
output current
short circuit protection
- Dissipation
Integrated digital inputs
- Number of inputs
- Isolation of inputs
- Input types
- Input voltage:
nominal value
signal at 0 (IEC 1131-2)
signal at 1 (IEC 1131-2)
- Input current at 24 V d.c.:
inputs Exx,02 to Exx,07
inputs Exx,00 and Exx,01
- Signal delay time
- Cable length:
unshielded
shielded
ICMK 14 F1
24 V d.c.
400 g
24 V d.c.
19.2 to 30 V
80 mA
400 mA
yes
no
-
-
-
5 W
8
1500 V a.c.
PNP and NPN
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
7 mA
9 mA
5 ms
300 m
500 m
3 – 12
ICMK 14 F1
ICMK 14 N1
120/230 V a.c.
24 V d.c.
800 g
400 g
120 or
24 V d.c.
230 V a.c.
97.75 to
19.2 to 30 V
126.5 V or
195.5 to 253 V
30 mA
80 mA
100 mA
400 mA
-
yes
yes
no
19.2 to 30 V
-
400 mA
-
yes
-
10 W
6 W
8
8
1500 V a.c.
1500 V a.c.
PNP and NPN
PNP and NPN
24 V d.c.
24 V d.c.
0 to + 5 V
0 to + 5 V
+ 15 to + 30 V
+ 15 to + 30 V
7 mA
7 mA
9 mA
9 mA
5 ms
5 ms
300 m
300 m
500 m
500 m
Advant Controller AC 31 / Issued: 01.99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents