18.2.23 Outdoor Heat Exchanger Sensor Abnormality (F40-21)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty outdoor unit PCB (main).
Abnormality Judgment
Continue for 5 seconds.
Troubleshooting