Panasonic S-22KA1E5S Service Manual page 189

Ka1e5 series, ya1e5 series, ua1e5 series, na1e5 series, ma1e5 series,
Hide thumbs Also See for S-22KA1E5S:
Table of Contents

Advertisement

15.7.3 95 x 95 Cassette (UA1E5 Series)
Air swing direction setting
Mode
Heat
Cool/Fan
Dry
Automatic mode judgment
Mode
Heat
Cool/Fan
Dry
Heating automatic air swing control according indoor unit heat exchanger temperature.
Condition
Normal
Deice
Hot start
Heat removal control
Thermostat OFF
Normal
Dew control
Thermostat OFF
Normal
Dew control
Thermostat OFF
Operation stop
Air swing direction setting
Condition
Indoor heat
exchanger
temperature
Deice
Hot start
Heat removal control
Thermostat OFF
Normal
Dew control
Thermostat OFF
Normal
Dew control
Thermostat OFF
Automatic mode judgment
Operation stop
60
C
o
30
C
o
Indoor heat exchanger temperature
Step 1
20°
20°
20°
20°
20°
Zone A
70°
Zone B
20° ~ 70°
Zone C
20°
20° ~ 70°
20° ~ 70°
20° ~ 70°
20°
Zone A
Zone B
Zone C
189
Manual
Step 2
Step 3
35°
50°
10°
10°
20°
20°
35°
50°
35°
35°
50°
35°
35°
35°
50°
35°
50°
Automatic
70°
20° ~ 50°
40° ~ 70°
20°
10°
10°
20°
20°
20° ~ 50°
40° ~ 70°
35°
20° ~ 50°
40° ~ 70°
30°
35°
20° ~ 50°
40° ~ 70°
20°
57
o
C
25
o
C
Step 4
70°
70°
70°
70°
70°
70°
20°
20°

Hide quick links:

Advertisement

Table of Contents