Panasonic S-22KA1E5S Service Manual page 130

Ka1e5 series, ya1e5 series, ua1e5 series, na1e5 series, ma1e5 series,
Hide thumbs Also See for S-22KA1E5S:
Table of Contents

Advertisement

2. Precautions in high humidity circumstance.
This air conditioner has been tested according to the "JIS Standard Conditions with Mist" and have been
confirmed that there are no faults. However, if it is operated for a long time in high humid atmosphere (dew point
temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according to
the following procedure:
Heat insulation material to be prepared...
Adiabatic glass wool with thickness 10 to 20
mm.
Stick glass wool on all air conditioners that are
located in ceiling atmosphere.
In addition to the normal heat insulation
(thickness: more than 8 mm) for refrigerant
piping (gas piping: thick piping) and drain
piping, add a further of 10 mm to 30 mm
thickness material.
Wall seal
When the outdoor unit is installed on a higher position than the indoor unit, install the trap so as not to instill
rain water into the wall by transmitting in piping.
Stuff the space among piping, the electric wire, and the drain hose with "Putty" and seal the penetration wall
hole.
Make sure that rain water do not instill into the wall.
11.8.7 ELECTRICAL WIRING
As to main power source and cable size of outdoor unit, read the installation instructions attached to the outdoor unit.
The units must be installed in accordance with applicable national and local regulations.
The units installed by a professional installer must be supplied from a dedicated electrical circuit.
Warning
All electric work must be carried out by a qualified technician according to proper technical standards for electrical work and
according to installation instructions for installation work.
If circuits with insufficient capacity are used, or if electrical work is not carried out properly, electric shocks or fire may result.
Be sure to install a current leakage breaker or circuit breaker to the main power supply, otherwise electric shocks may result.
Caution
Be sure to connect the unit to secure earth connection. (with a earth resistance of 100 Ω or less).
Caution
If the earthing work is not carried out properly, electric shocks may result.
Wiring shall be connected securely using specified cables and fix them securely so that external force of the cables may not
Warning
transfer to the terminal connection section. Imperfect connection and fixing leads to fire, etc.
1. Select a power source that is capable of supplying the current required by the air conditioner.
2. Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should
disconnected all poles with a contact separation of at least 3 mm.
3. Always ground the air conditioner with a grounding wire and screw to meet the LOCAL REGULATIONS.
4. Be sure to connect the wires correctly to terminal board with connecting the crimp type ring terminal to the wires.
5. Be sure to turn off the main power before installing and connecting the remote control.
If momentarily turning on the power supply for both the indoor and outdoor units, do not turn the power off after at least 1
minute has passed. (For the system's automatic setting.)
Note
Turning off the power supply on the way may cause an abnormal operation.
Pipe down
Indoor
unit
✳ Put the incision at the trap part of the heat insulator
(for water drain)
130
Putty
Pipe
Trap
Drain pipe
Incision

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents