18.2.20 Outdoor Fan Motor (DC Motor) Mechanism Locked (F35-02)
Malfunction Decision Conditions
•
The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine
abnormal fan motor (feedback of rotation > 2550rpm or < 20rpm).
Malfunction Caused
•
Operation stops due to short circuit inside the fan motor winding.
•
Operation stops due to breaking of wire inside the fan motor.
•
Operation stops due to breaking of fan motor lead wires.
•
Operation stops due to fan motor Hall IC malfunction.
•
Operation error due to faulty outdoor unit PCB (inverter).
Abnormality Judgment
•
Continue 2 times in 30 minutes.
Troubleshooting