18.2.2
Indoor Fan Motor (DC Motor) Mechanism Locked (F17-02)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine
abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm).
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to fan motor Hall IC malfunction.
Operation error due to faulty indoor unit PCB (main).
Abnormality Judgment
Fan motor runs for 5 seconds and stops for 25 seconds, and repeat continuously for 7 times.
Troubleshooting