GE VersaPoint IC220PBI002 User Manual page 96

Profibus-dp niu
Table of Contents

Advertisement

6
Structure of station status 2 (byte 1)
Bit
Value
0
1
1
1
2
1
3
1
4
1
5
1
6
0
7
1
Structure of station status 3 (byte 2)
Bit
Value
0 to
0
6
7
1
6-16
VersaPoint™ I/O System Profibus-DP NIU User's Manual – August 2005
Meaning
The DP slave must be parameterized again.
A diagnostic error message has been generated. The DP slave will
not operate until the error has been removed (static diagnostic
message).
The bit always has the value 1 if the DP slave with this Profibus
address is present.
Response monitoring is activated for this DP slave.
The DP slave has received the "FREEZE" control command. This
bit is only updated if you change another diagnostic message too.
The DP slave has received the "SYNC" control command.
Bit always has the value 0.
The DP slave is deactivated, i.e., removed from the current
process
Meaning
Always 0.
There are more error messages than the DP slave can save.
GFK-1911B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Versapoint ic220pb001Versapoint ic220pbo002

Table of Contents