Error Type
(FS on, # of
FN pulses)
4
6-8
VersaPoint™ I/O System Profibus-DP NIU User's Manual – August 2005
Error No.
Meaning
(FS off, #
of FN
pulses)
Errors Within the Station
1
An error has occurred
during data transmission
between the VersaPoint
modules (data IN).
2
An error has occurred
during data transmission
between the VersaPoint
modules (data OUT).
3
An error has occurred
during data transmission
between the VersaPoint
modules.
4
The VersaPoint module is
not ready.
5
The replaced VersaPoint
module does not
correspond to the length
code or ID code.
6
An additional VersaPoint
module has been
detected in the station.
Remedy
Determine the exact error location
locally using the LEDs or the
device-specific diagnostics in your
control system.
Check the connection between
the devices indicated.
Determine the exact error location
locally the LEDs on the I/O
modules, or the device-specific
diagnostics in your control
system.
Check the connection between
the device indicated.
The exact error location can be
detected locally using the flashing
LEDs on the I/O modules.
Check the connection preceding
the indicated devices.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Check the indicated devices.
A new VersaPoint module does
not correspond to the NIU
configuration. Determine the
exact error location using the
device-specific diagnostics in your
control system.
Remove the module from the
station.
Check the configuration of the
station. If the configuration is
correct, switch off the current
supply for a short period, so that
the new configuration is accepted.
GFK-1911B