Segment Circuit: U - GE VersaPoint IC220PBI002 User Manual

Profibus-dp niu
Table of Contents

Advertisement

Segment Circuit: U

A segment circuit or auxiliary circuit with segment voltage U
at a supply terminal (power terminal or segment terminal). It is fed through all
subsequent modules as far as the next supply terminal.
NIU
Function of U
Voltage of U
Current carrying
capacity of U
The segment circuit supplies all modules that need to be separately switchable
from the main voltage e.g., on an emergency stop. This includes discrete input
modules without individual short-circuit protection, discrete output modules, and
auxiliary supply voltage for controlling power switches and contactors. The
segment circuit can be switched off or fused using the emergency stop or segment
terminals. It has the same ground reference as the main circuit. This means that
emergency stop circuits or circuits with different fuses can be created within the
station without external wiring.
Generation of U
There are various ways of providing the segment voltage U
1. You can supply the segment voltage at the NIU or at a power terminal.
2. You can tap the segment voltage from the main power at the NIU or a power
terminal using a jumper or a switch.
3. You can use a segment terminal and tap the segment voltage from the main
power.
With 120V and 230V voltage levels, segments cannot be created. In this
case, only the main circuit is used.
GFK-1911B
Chapter 5 Power for the Station
S
Power Terminal
You can use several segment terminals within a main circuit, and
S
therefore segment the main circuit. It has the same ground
reference as the main circuit. This means that circuits with
different fuses can be created within the station without external
wiring.
24VDC maximum.
S
8A, maximum (total current with the main circuit). If the limit value
of a voltage jumper U
S
U
), a new power terminal must be used. (See summary of I/O
M
module current consumptions in this chapter).
S
starts at the NIU or
S
Segment Terminal
or U
is reached (total current of U
M
S
:
S
5
and
S
5-5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Versapoint ic220pb001Versapoint ic220pbo002

Table of Contents