Error Type
Error No.
(FS on, # of
(FS off, # of
FN pulses)
FN pulses)
3
Configuration Errors in the VersaPoint Station
GFK-1911B
Chapter 6 Diagnostics
Meaning
1
The VersaPoint module
is not enabled for
operation on the NIU.
2
The length code of the
VersaPoint module
corresponds to a length
of 0 bytes.
3
The length code of the
VersaPoint module
corresponds to a length
of more than 32 bytes.
4
Invalid module type
present in the station.
5
The sum of the process
data for the local bus is
greater than 250 bytes.
6
There are more than 64
VersaPoint modules
connected.
7
The sum of the process
data for the Profibus
inputs and outputs is
greater than 176 bytes
(184 bytes in DP/V0
mode).
8
More than 8 PCP slaves
are connected.
(IC670PBI002)
Remedy
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Remove the module from the
station.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Check the module and, if
necessary, remove it from your
configuration.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Remove the module from the
station.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Remove the module from the
station.
Check the amount of process
data and reduce the number of
modules in the station.
Check whether more than 64
VersaPoint are present in the
station and reduce the number of
modules.
Remove the modules from the
station.
Reduce the number of PCP
modules in the station
6
6-7