Connecting Shielded Cables

Observe the following when installing shielding:
Strip the outer cable sheath to the desired length (#1a below). The appropriate
length depends on the connection position of the wires and whether there
should be a large or a small space between the connection point and the
shield connection.
Shorten the braided shield to 15mm (0.6 in.) (#1 above).
Fold the braided shield back over the outer sheath. (#2 above)
Remove the protective foil.
Strip 8mm (0.3in.) off the wires. (#2 above)

Connecting Shielded Cables to the Shielded Terminal Strip

Open the shield connector (#3 above).
Check the orientation of the shield clamp in the Shielded Terminal Strip and
change its position if necessary (see below for instructions).
Place the cable with the folded braided shield in the shield connector. (#4
above)
GFK-1911B
Chapter 4 Installation
4
4-11