GE VersaPoint IC220PBI002 User Manual page 41

Profibus-dp niu
Table of Contents

Advertisement

Internal Structure of the Connector
A
B
C
D
The dark lines shown on connectors B and D above indicate jumper
connections. These jumpers are internal to the connectors.
The shield connector is jumpered through the shield connection. All other
connectors are jumpered through module point connection.
To avoid a malfunction, only snap a suitable connector on a module that is
appropriate for this connector. Refer to the module-specific data sheet to
select the correct connectors.
A supply connector must not be placed on a module that is to be used
with an extended connector. This will cause a short circuit between
two signal module points (1.4 - 2.4).
Place only supply connectors on supply modules. Do not use the
standard connectors! When the terminal points are jumpered in the
supply connector, power is carried through the jumpering in the
connector and not through the printed circuit board of the module.
GFK-1911B
Chapter 3 VersaPoint Modules
Standard connector (IC220TBK082, 085)
Connector for power and segment terminals (IC220TBK087)
Shield connector (IC220TBK061) for analog modules
Extended connector (IC220TBK122, TBK123)