Mechanical Demands

Mechanical Demands
Vibration test
Sinusoidal vibrations according to
IEC 60068-2-6
Shock test according to IEC
60068-2-27

Noise Immunity Test

Noise Immunity Test
Please refer to the module data sheets for additional information.
In Accordance with EN 50082-2
Electrostatic Discharge (ESD)
Electromagnetic Fields
Bursts
Conducted Interference
In Accordance with EN 50082-2
Noise Emission of the Housing
A-4
VersaPoint™ I/O System Profibus-DP NIU User's Manual – August 2005
2g load, 2 hours for each space direction
(Low-level signal)
2g load, 2 hours for each space direction
(Power level)
25g load for 11ms, half sinusoidal wave, three
shocks in each space direction and orientation.
EN 61000-4-2 / IEC 61000-4-2
Criteria B, 4kV contact discharge, 8kV air
discharge
ENV50140 / ENV50204
Criteria A, Field Strength: 10V/m
EN 61000-4-4 / IEC 61000-4-4 Criteria A, All
Interfaces:2kV
ENV 50141, Criteria A, Test voltage 10V
EN 5011, Class A
GFK-1911B