SITRANS F C MASSFLO
3.
Electrical connection
3.1 Electrical connection
IP 20 & IP 65
3. Electrical connection
IP 20
IP 65
SFIDK.PS.028.R1.02
1. Connection terminals to:
•
Power supply
•
In- and output
2. Connection terminals to:
MASS 2100 sensor
Intrinsically safe terminals!
It is an absolute requirement that the wires/
terminals of the intrinsically safe circuits can-
not get into contact with the wires of the other
cables. The distance between cables/wires
therefore must be at least 50 mm.
It is recommended to fasten the cables/wires in
a way that they, even in case of an error, cannot
get into contact with each other. Make the wire
ends as short as possible.
11