6.4.10 Measured Value Display

The transmitter display can show the output current in mA, the output current in 0-100%, or the input
pressure in a selected engineering unit. To select the displayed parameter and, if input pressure is desired,
the engineering unit:
1. In the Online menu, press 3 Device Setup.
2. In the Device Setup menu, press 4 Detailed Setup.
3. In the Detailed Setup menu, press 4 Device Information
4. In the Detailed Information menu, press 5 Local Meter.
5. In the Local Meter menu, press 3 Local Display Units.
6. Cursor to the desired display unit. The current selection is shown at the top of the list and slightly
offset to the left.

6.4.11 Select Pressure Engineering Units

This selection is used to choose the engineering unit assigned to the input pressure.
1. In the Online menu, press 3 Device Setup.
2. In the Device Setup menu, press 3 Basic Setup.
3. In the Basic Setup menu, press 2 (Engineering) Unit.
4. The presently selected unit is shown at the top of the list and slightly offset to the left. Cursor to the
desired engineering unit using the Communicator's Up and Down Arrow keys. Press ENTER to save
the selection and return to the previous menu. Press ESC to return to the previous menu without
saving a new selection.

6.4.12 Display/Bargraph

In the display mode, the selection made in Section 6.4.10 will appear in the lower right quadrant of the
display. The factory setting of the bargraph function is "off."
1. In the Online menu, press 3 Device Setup.
2. In the Device Setup menu, press 4 Detailed Setup.
3. In the Detailed Setup menu, press 4 Device Information.
4. In the Detailed Information menu, press 5 Local Meter.
5. In the Local Meter menu, press 4 Bargraph.
6. The current status of the bargraph is shown at the top of the list and slightly offset to the left. Cursor
to the desired status: Not Active or Active. Press ENTER to save the selection and return to the
previous display. Press ESC to return to the previous menu without saving a new selection.
November 2005
On-Line Operation
6-25