5.6.21 DR 7 - Replacement Values for DO 1 to 8 with Fault or Output Disable

Normally, the outputs are reset with a SIMATIC CPU STOP. This behavior
corresponds with the default setting.
If it makes sense to set an output with a SIMATIC CPU STOP, you can define it
with this parameter.
E.g. Digital output 1 (DO1) is determined with bit 0:
If bit 0 is 0 then DO1 is also 0 with OD signal.
If bit 0 is 1 then DO1 is 1 with OD signal.
The digital output 1 (DO2) is determined with bit 1:
If bit 1 is 0 then DO2 is also 0 with OD signal.
If bit 1 is 1 then DO2 is 1 with OD signal.
etc.
!
Warning notice
If an output is to be set with the SIMATIC CPU STOP then you must ensure that it
does not lead to a hazardous situation.

5.6.22 DR 7 - Replacement Values for Digital Outputs with Operating Error

Normally, the outputs are reset when there is a module group fault (operating
error). This behavior corresponds with the default setting.
If it makes sense to set an output with a fault, you can define it with this parameter.
E.g. Digital output 1 (DO1) is determined with bit 0:
If bit 0 is 0 then DO1 is also 0 with fault.
If bit 0 is 1 then DO1 is 1 with fault.
The digital output 1 (DO2) is determined with bit 1:
If bit 1 is 0 then DO2 is also 0 with fault.
If bit 1 is 1 then DO2 is 1 with fault.
etc.
Warning
If an output is to be set with the fault (operating error) then you must ensure that it
does not lead to a hazardous situation.
5-66
SIWAREX FTC