7.6 Message list Data and Operating Errors

Error

Data and operating
No.
errors
- Meaning
1
Unknown command
code
2
Action not permitted
in service operation
3
Service operation
cannot be deactivated
sine the assembly is
not adjusted
4
Action only permitted
in service operation
5
Calibration parameter
transfer with active
write protect not
permitted
6
Adjustment command
with active write
protect not permitted
7
Download not
possible since write
protect is active
11
Transmission of the
data record or
command is not
permitted in
continuous operation
7-100 SIWAREX FTC
Explanation
The SIWAREX does not recognize the command code or the
data record in the parameterized mode or is unable to process
the command or data record in the current operating state.
Only certain commands or data entries are permitted in
service operation. The last command or the last sent data
cannot be accepted by the scale in service operation.
The following commands are not permitted:
-
Start totalization
-
Taring (22, 24)
-
Output log (31 to 35)
-
Start/Stop Trace (70, 71)
Switch to normal operation.
A non-adjusted module group cannot be switched to normal
operation. Fist, adjust the scale and then you can get out of
service operation. A theoretical adjustment can be performed
with the SIWATOOL FTC_B.
Only certain commands or data entries are permitted in normal
operation. The last command or the last sent data cannot be
accepted by the scale in normal operation. Switch to service
operation.
The following activities can only be performed in service
operation:
-
Load factory settings command (8)
-
Switch service operation off (2)
-
Adjustment commands (3, 4, 5, 6, 7)
-
Delete / Format MMC (72 to 75)
-
Send DR 3
The calibration parameters (DR 3) may only be changed if the
write protect is not active (switch on the front moved to down
position). First deactivate the write protection.
This also applies for the internal data record DR 26. Attention!
A pre-calibrated scale will lose its calibration.
The adjustment commands can only be executed when the
write protect is inactive (switch on the front in the down
position). First deactivate the write protection. Attention! A pre-
calibrated scale will lose its calibration.
Downloading the firmware may only be done if the write
protection is inactive (switch on front down). First deactivate
the write protection. Attention! A pre-calibrated scale will lose
its calibration.
The data record or the command is not permitted to be
activated during the totalizing.