Connection system
6.1 Power connection
Current-carrying capacity for power and signal cables
The current-carrying capacity of PVC/PUR-insulated copper cables is specified for routing
types B1, B2 and C under continuous operating conditions in the table with reference to an
ambient air temperature of 40 °C. For other ambient temperatures, the values must be
corrected by the factors from the "Derating factors" table.
Table 6- 1
Cross section
[mm
Electronics (according to EN 60204-1)
0,20
0,50
0,75
Power (according to EN 60204-1)
0,75
1,00
1,50
2,50
4
6
10
16
25
35
50
70
95
120
Power (according to IEC 60364-5-52)
150
185
> 185
Table 6- 2
Ambient air temperature [°C]
30
35
40
45
50
55
60
224
Cable cross section and current-carrying capacity
Current-carrying capacity rms; AC 50/60 Hz or DC for routing type
]
B1 [A]
2
-
-
-
8,6
10,3
13,5
18,3
24
31
44
59
77
96
117
149
180
208
-
-
Values must be taken from the standard
Derating factors for power and signal cables
B2 [A]
4,3
7,5
9
8,5
10,1
13,1
17,4
23
30
40
54
70
86
103
130
165
179
-
-
Derating factor according to EN 60204-1 Table D1
1,15
1,08
1,00
0,91
0,82
0,71
0,58
Configuration Manual, (PFT7S) 01/2009, 6SN1197-0AD13-0BP2
C [A]
4,4
7,5
9,5
9,8
11,7
15,2
21
28
36
50
66
84
104
125
160
194
225
344
392
1FT7 Synchronous Motors