Siemens SIMOVERT 6SE7024-1EB85-0AA0 Operating Instructions Manual page 81

Simovert 6se70 series master drives common rectifier size b and c
Table of Contents

Advertisement

Available languages

Available languages

11.98
Rated voltage U
n
chained in V
(A.C.)
rms
600
575
525
500
Table 4.2
On and off thresholds for units 6SE70xx-xFx8x
S1
L1
L2
460
600
440
575
415
525
400
500
380
---
230
---
Size B
Fig. 4.1 Selector switches S1 and S3 on the A23 board
The following commissioning steps must be carried out after connecting the unit
(as detailed in Chapter 3):
♦ Set the rated mains voltage with S1 (Piano DIP switch) (press the corresponding lever of the switch towards
the module). It is only permissible to select one voltage (S3 also open).
The 200 V voltage range is activated by closing DIP-fix jumper S3 (by means of S1), whereby all the levers
of S1 must be open.
Works setting:
for 200-230V and 380-480V units = 400V
for 500-600V units = 500V
♦ The status of the bridging relays can be switched through to the "Warning" output (terminal X36) with the
jumper S2 (DIP-Fix). When S2 is open, the "Warning" relay is opened only in the event of the excess
temperature pre-warning.
Works setting:
S2 open
♦ Switch on the mains and electronic power supply.
♦ Enable the converter.
Siemens AG
6SE7087-6AC85-0AA0
Common Rectifier
Operating instructions
Nominal dc link voltage values
U
in V=
nd
(set parameter P071 on the
SIMOVERT Master Drive)
789
756
690
657
S3
1
2
3
S1
4
5
6
1 0
Position on A23
460 V position also for 480 V, S3 for 200 V
On threshold
of U
in V=
d
663
635
580
552
S1
L1
L2
460
600
440
575
415
525
400
500
380
---
230
---
Size C
Start-up
Off threshold
of U
in V=
d
546
523
478
455
S3
6
5
4
S1
3
2
1
0 1
Position on A23
4-3
ENGLISH