Connection
♦ Fan for additional power supply in the case of 36A units (6SE7024-1xB85)
(
not a customer terminal
Connector X20
Connector X20
Pin 1
DC 24V via a controlled voltage limiter
Pin 2
Reference potential
Table 3.7
Fan connection
♦ Connecting control lines of optional modules (in preparation)
When installed, control lines must be shielded and isolated from the power cables, laying them at a minimum
distance of 20 cm. The shield must be connected on both sides. On the unit's housing, the shield is connected
with shield clamps. Handling of these clamps is shown in Figure 3.3.
When they intersect, control and power cables must be laid at an angle of 90°.
Cable binder
Adapt length
to design
Shield
Figure 3.3 Connecting the control lines and handling the shielding clamps
Use must be made of the 'EMC shielding housing' option if so many control lines are needed that two shielding
clamps are not enough.
Order numbers:
♦ Design B
6SE7090-0XB87-3CA0
♦ Design C
6SE7090-0XC87-3CA0
3-6
ENGLISH
)
Connector
Slide on shield
and secure with
shrink-on tubing,
for example
Do not bend
spring over
35
Function description
NOTE
Fitting the shielding clamp
∅ ≤ 15mm
Releasing the shielding clamp
∅ ≤ 7,5mm
∅ ≤ 5mm
Manually or using a screwdriver,
press the clamp together and extract
it in the updown direction.
Caution!
The clamps are sharp-edged!