Motor Learned Data - GE M60 Instruction Manual

Motor protection system ur series
Hide thumbs Also See for M60:
Table of Contents

Advertisement

6.4 RECORDS
PATH: ACTUAL VALUES
 MOTOR LEARNED
 DATA
The
NUMBER OF RECORDS
ware or via HTTP with Internet Explorer. The
were cleared.
The values for the last motor start-running-stop cycle are available in this menu. The
value is computed during motor running conditions at intervals defined by the
This value is updated whenever new values become available.
Up to 250 motor learned data records are stored and accessible via the EnerVista UR Setup software through the following
methods.
6
Select the Actual Values > Records > Motor Learned Data menu item.
Select the Maintenance > Retrieve File menu item and open the "MotorLD.htm" file.
Select the Maintenance> Retrieve File menu item and open the "MotorLD.txt" file.
The following historical data is displayed in the motor learned data records.
Report number.
Report date.
Learned acceleration time (in seconds).
Learned starting current (in multiples of full load current).
Learned starting capacity (in percent).
Learned average motor load (in multiples of full load current).
Learned run time after start (in hours).
The learned values for acceleration time and effective starting current are the maximum of the individual values acquired
for the last N successful starts, where N is defined by the
The learned value for the starting thermal capacity is calculated using the maximum of the last motor start measurements
and incorporates a security margin defined by the

THERMAL MODEL
START INHIBIT TCU MARGIN
24, 23, 27, 26, and 21%, respectively, with the
27% × 1.25 = 33.75%.
Learned values associated with motor acceleration require the acceleration time function to be enabled. The
learned features are not be used until at least N + 1 successful motor starts have occurred.
NOTE
6-24


RECORDS

MOTOR LEARNED DATA

NUMBER OF RECORDS:
0
LAST CLEARED DATE:
MESSAGE
2007/07/14 15:40:16
LAST ACCELER. TIME
MESSAGE
LEARNED: 0.00 s
LAST STARTING CURR.
MESSAGE
LEARNED: 0.00 x FLA
LAST STARTING CAPAC.
MESSAGE
LEARNED: 0%
LAST AVRG MOTOR LOAD
MESSAGE
LEARNED: 0.00 x FLA
LAST RUN t AFT. STRT
MESSAGE
LEARNED: 00:00 hr
value indicates how many records are available to the user through the EnerVista UR Setup soft-
LAST CLEARED DATE
SETTINGS
setting. For example, if the thermal capacity used for the last five starts is
START INHIBIT TCU MARGIN
M60 Motor Protection System
Range: 0 to 250
Range: date and time in standard format
Range: value in seconds
Range: value in multiples of full load current
Range: value in percentage
Range: value in multiples of full load current
Range: value in hours
value indicates the last time that learned data records
MOTOR LOAD AVERAGE CALC. PERIOD
NUMBER OF STARTS TO LEARN

GROUPED ELEMENTS
= 25%, then the
6 ACTUAL VALUES
6.4.3 MOTOR LEARNED DATA
LAST AVRG MOTOR LOAD LEARNED
setting.
setting.
SETTING GROUP 1(6)
MOTOR
LEARNED STARTING CAPACITY