2.2 SPECIFICATIONS
PHASE UNDERVOLTAGE
Voltage:
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
2
Curve multiplier:
Timing accuracy:
Operate time:
AUXILIARY UNDERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
Curve multiplier:
Timing accuracy:
Operate time:
PHASE OVERVOLTAGE
Voltage:
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Operate time:
Timing accuracy:
NEUTRAL OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Reset delay:
Timing accuracy:
Operate time:
AUXILIARY OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Reset delay:
Timing accuracy:
Operate time:
2-12
Phasor only
0.000 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse;
Definite Time (0.1s base curve)
Time dial = 0.00 to 600.00 in steps of
0.01
Operate at < 0.90 × pickup
±3.5% of operate time or ±4 ms (which-
ever is greater)
<30 ms at 0.9 pickup at 60 Hz for Defi-
nite Time mode
0.000 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse, Definite Time
Time Dial = 0 to 600.00 in steps of 0.01
±3% of operate time or ±4 ms
(whichever is greater)
<30 ms at 0.9 pickup at 60 Hz for Defi-
nite Time mode
Phasor only
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 in steps of 0.01 s
< 30 ms at 1.10 × pickup at 60 Hz
±3% or ±4 ms (whichever is greater)
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 s in steps of 0.01 (definite
time) or user-defined curve
0.00 to 600.00 s in steps of 0.01
±3% or ±20 ms (whichever is greater)
< 30 ms at 1.10 × pickup at 60 Hz
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0 to 600.00 s in steps of 0.01
0 to 600.00 s in steps of 0.01
±3% of operate time or ±4 ms
(whichever is greater)
< 30 ms at 1.10 × pickup at 60 Hz
M60 Motor Protection System
2 PRODUCT DESCRIPTION
NEGATIVE SEQUENCE OVERVOLTAGE
Pickup level:
0.000 to 1.250 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0 to 600.00 s in steps of 0.01
Reset delay:
0 to 600.00 s in steps of 0.01
Time accuracy:
±3% or ±20 ms, whichever is greater
Operate time:
< 30 ms at 1.10 × pickup at 60 Hz
MOTOR START SUPERVISION
Maximum no. of starts:
1 to 16 in steps of 1
Monitored time interval: 1 to 300 minutes in steps of 1
Time between starts:
0 to 300 minutes in steps of 1
Restart delay:
0 to 50000 seconds in steps of 1
UNDERFREQUENCY
Minimum signal:
0.10 to 1.25 pu in steps of 0.01
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup + 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% or 4 ms, whichever is greater
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
OVERFREQUENCY
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup – 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% or 4 ms, whichever is greater
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
BREAKER FAILURE
Mode:
1-pole, 3-pole
Current supervision:
phase, neutral current
Current supv. pickup:
0.001 to 30.000 pu in steps of 0.001
Current supv. dropout:
97 to 98% of pickup
Current supv. accuracy:
0.1 to 2.0 × CT rating: ±0.75% of reading or ±2% of rated
(whichever is greater)
above 2 × CT rating:
±2.5% of reading
REDUCED VOLTAGE STARTING
Mode:
current only, current and timer, current or
timer
Transition level:
25 to 300% of FLA in steps of 1
Timer:
1.0 to 600.0 seconds in steps of 0.1
Timing accuracy:
±50 ms