Advertisement

5.2 PRODUCT SETUP
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
PRODUCT SETUP
 XSWI
 CONFIGURATION
The
CLEAR XSWI1 OpCnt
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
5
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
NOTE
functionality.
h) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 WEB SERVER
 HTTP PROTOCOL
The M60 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Mozilla Firefox. This feature is available only if the M60 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the M60 "Main Menu". Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be
accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web
browser on the computer simply by entering the IP address of the M60 into the "Address" box on the web browser.
i) TFTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 TFTP PROTOCOL
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the M60 over a network. The M60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the M60 contains a list and description of all available files (event records, oscillography, etc.).
5-34

COMMUNICATIONS
XSWI 1ST.LOC OPERAND
Off
XSWI 2ST.LOC OPERAND
MESSAGE
Off
XSWI24ST.LOC OPERAND
MESSAGE
Off
CLEAR XSWI 1OpCnt:
MESSAGE
No
CLEAR XSWI 2OpCnt:
MESSAGE
No
CLEAR XSWI24OpCnt:
MESSAGE
No
setting represents the disconnect switch operating counter. As disconnect switches operate by

COMMUNICATIONS
HTTP TCP PORT
NUMBER:

COMMUNICATIONS
TFTP MAIN UDP PORT
NUMBER:
TFTP DATA UDP PORT 1
MESSAGE
NUMBER:
TFTP DATA UDP PORT 2
MESSAGE
NUMBER:
M60 Motor Protection System


IEC 61850 PROTOCOL
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: No, Yes
Range: No, Yes
Range: No, Yes

WEB SERVER HTTP PROTOCOL
Range: 1 to 65535 in steps of 1
80

TFTP PROTOCOL
Range: 1 to 65535 in steps of 1
69
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
5 SETTINGS