APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 4 of 59)
ADDR
REGISTER NAME
160D
Reserved
160E
Reserved
Ethernet Fibre Channel Status (Read/Write)
1610
Ethernet Primary Fibre Channel Status
1611
Ethernet Secondary Fibre Channel Status
Data Logger Actuals (Read Only)
1618
Data Logger Channel Count
1619
Time of Oldest Available Samples
161B
Time of Newest Available Samples
161D
Data Logger Duration
Stator Differential Actuals (Read Only)
1660
Generator Differential Iad
1662
Generator Restraint Iar
1664
Generator Differential Ibd
1666
Generator Restraint Ibr
1668
Generator Differential Icd
166A
Generator Restraint Icr
166C
Stator Differential CT Primary
Sensitive Directional Power Actuals (Read Only) (2 modules)
1680
Sensitive Directional Power 1 Power
1682
Sensitive Directional Power 2 Power
Field Unit RTD Actuals (Read Only) (8 modules)
16C0
Field RTD 1 Value
16C1
...Repeated for Field RTD 2
16C2
...Repeated for Field RTD 3
16C3
...Repeated for Field RTD 4
16C4
...Repeated for Field RTD 5
16C5
...Repeated for Field RTD 6
16C6
...Repeated for Field RTD 7
16C7
...Repeated for Field RTD 8
Field Unit Transducer Actuals (Read Only) (8 modules)
16C8
Field Transducer 1 Value
16CA
...Repeated for Field Transducer 2
16CC
...Repeated for Field Transducer 3
16CE
...Repeated for Field Transducer 4
16D0
...Repeated for Field Transducer 5
16D2
...Repeated for Field Transducer 6
16D4
...Repeated for Field Transducer 7
16D6
...Repeated for Field Transducer 8
Source Current (Read Only) (6 modules)
1800
Source 1 Phase A Current RMS
1802
Source 1 Phase B Current RMS
1804
Source 1 Phase C Current RMS
1806
Source 1 Neutral Current RMS
1808
Source 1 Phase A Current Magnitude
180A
Source 1 Phase A Current Angle
180B
Source 1 Phase B Current Magnitude
180D
Source 1 Phase B Current Angle
180E
Source 1 Phase C Current Magnitude
1810
Source 1 Phase C Current Angle
1811
Source 1 Neutral Current Magnitude
1813
Source 1 Neutral Current Angle
1814
Source 1 Ground Current RMS
1816
Source 1 Ground Current Magnitude
GE Multilin
RANGE
0 to 65535
0 to 65535
0 to 2
0 to 2
0 to 16
0 to 4294967295
0 to 4294967295
0 to 999.9
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 50000
-2147483647 to 2147483647
-2147483647 to 2147483647
-32768 to 32767
-32.768 to 32.767
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
0 to 999999.999
M60 Motor Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F500
---
1
F500
---
1
F134
---
1
F134
channel
1
F001
seconds
1
F050
seconds
1
F050
days
0.1
F001
A
0.001
F060
A
0.001
F060
A
0.001
F060
A
0.001
F060
A
0.001
F060
A
0.001
F060
---
1
F060
W
1
F060
W
1
F060
°C
1
F002
---
0.001
F004
A
0.001
F060
A
0.001
F060
A
0.001
F060
A
0.001
F060
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
A
0.001
F060
DEFAULT
0
0
0 (Fail)
0 (Fail)
B
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
B-11