Carel humiSteam UE005 User Manual page 59

Humisteam series
Hide thumbs Also See for humiSteam UE005:
Table of Contents

Advertisement

code display and
code var. I89 meaning
symbol
EA
3002Hex
foam
E2
3010Hex
memory backup fails internal memory
Mn
1001Hex
end of cylinder life
EU
2001Hex
cylinder full
EC
1002Hex
high conductivity
E3
-
2002Hex
failed connection of
modulating signal
E_
2020Hex
low room humidity
(low
temp. when using
temperature probe)
--
E
2010Hex
high room humidity
(high
temp. when using
temperature probe)
SU
2040Hex
serial disconnected
Pre/Cln -
cylinder cleaning
started signal
dr
-
cylinder drain
activated
dr / TOT -
complete drain due
to inactivity
AF
antifoam active
Press ESC once to mute the buzzer, press ESC a second time to reset the alarm.
(*) Quick flash: 0.2 seconds ON and 0.2 seconds OFF
Slow flash: 1 second ON and 1 second OFF
causes
solution
excessive foam in
1. drain the water
the cylinder during
supply lines
boiling.
2. clean the cylinder
the formation of
3. check for the
foam is generally
presence of softeners
due to the presence
(in this case, use
of surfactants in the
another type of water
water (lubricants,
or reduce the
solvents, detergents,
softening)
water treatment
agents, softeners)
or an excessive
concentration of
dissolved salts.
if the problem persists,
error
contact the CAREL
service center
the cylinder has
exceeded the limit of
2000 hours, replace the
cylinder
excessive water
with the machine off:
level when unit
1. check for any
producing steam
leaks from the fill
electrovalve or the
condensate return
pipe
2. check that the level
sensors are clean
total shut-down pipe
2. check that the level
sensors are clean
total shut-down
high supply water
1. check water
conductivity
conductivity
2. if the problem
persists, change the
source of supply water
or install a
suitable treatment
system
(demineralisation, even
partial).
N.B.: the problem will
not be resolved
by softening the
supply water.
check the reference
signal in 4 to 20 mA or
2 to 10V mode or NTC)
check the probe
operation and the limit
set on parameter P2
check the probe
operation and the limit
set on parameter P3
21
reset
alarm relay
effect
(press)
activation
ESC
no
signal only
--
no
signal only
reset hour
yes
humidification
counter
stopped
--
no
signal only
AUTO
no (b5)
signal only
yes (b6)
humid.
stopped
ESC
yes
humidification
stopped
AUTO
yes
humidification
stopped
AUTO
yes
humidification
stopped
AUTO
--
--
--
--
--
--
--
--
--
--
--
"UE BASIC" +08C0042EZ - rel. 1.0 - 16.10.2017
ENG
red LED signal on
board (*)
(if terminal not
connected)
9 slow flashes
6 fast flashes
8 fast flashes
8 slow flashes
5 fast flashes
7 slow flashes
9 fast flashes
10 fast flashes
2 slow flashes
none
none
(both codes
alternate on
display)
none