Steam Distribution; Carel Jet Distributors (Sdpoem00**); Carel Linear Distributors For Air Ducts (Dp***Dr0); Carel Steam Blowers (Vsdu0A*, Models Ue003 To Ue015 Only) - Carel humiSteam UE005 User Manual

Humisteam series
Hide thumbs Also See for humiSteam UE005:
Table of Contents

Advertisement

ENG

3.1 CAREL jet distributors (SDPOEM00**)

These can be fitted horizontally or vertically (hole facing upwards).
See page 31 for the models of distributors.
Assembly instructions (see Fig.3.a ):
make a series of holes on the wall according to the distributor drilling
template;
insert the distributor;
fasten the flange using 4 screws.
50
31,5
A
B
Key:
A. steam inlet
B. condensate drain
C. steam outlet.
the dimensions of the hole vary depending on the models of
distributor:
model SDPOEM0000: hole made manually, up to 30 mm (1.2") in
diameter);
model SDPOEM0012: diameter of the hole 12 mm (0.5");
model SDPOEM0022: diameter of the hole 22 mm (0.9").
D
drilling template
Note: if steam hoses with an inside diameter of 30 mm (1.2") are
used, remove the 22 mm (0.9") steam inlet section.
3.2 CAREL linear distributors for air ducts
(DP***DR0)
Install away from obstacles (curves, branches, changes in cross-section,
grills, filters, fans).
Minimum distance between the distributor and the obstacle: 1/1.5 m
(3.3/4.9 ft). Increase the distance if:
the air speed increases in the duct,
the relative humidity of the air increases before and after
humidification,
the turbulence decreases.
See page 33 for installation examples.
Assembly instructions (see Fig.3.b ):
make a series of holes on the wall according to the distributor drilling
template (included in the packaging with the distributor);
insert the distributor with the steam hole
"UE BASIC" +08C0042EZ - rel. 1.0 - 16.10.2017

3. STEAM DISTRIBUTION

50
31,5
D
C
C
B
A
Fig. 3.a
3
4
5
X
Key:
1 "L"-shaped mounting support (where featured)
2 flange gasket
3 steam inlet (ØA)
4 condensate drain (ØB)
5 screw diameter (see the instruction sheet supplied with the distributor)
6 length (depending on the model of distributor, see par. "10.5" page 38)
7 angle (around 2°) for draining the condensate.
8 diameter of the hole on the wall (ØY)
Dimensions in mm (in)
DP***D22R0
ØA
22 (0.9")
ØB
10 (0.4")
ØY
58 (2.3")
Ø
35 (1.4")
X
68 (2.7")
Important:
1.
fit the distributor at a slight incline (at least 2°, to prevent the return
of condensate);
2.
the "L"-shaped mounting support (see part 1 Fig. 3.c) is supplied with
steam distributor models from DP085* to DP025*. For shorter lengths,
the support can be supplied as an option (code 18C478A088).
3.3 CAREL steam blowers (VSDU0A*,
models UE005 to UE015 only)
Steam distributors for humidifiers with flow rates up to 15 kg/h. Can be
connected on top of the humidifier, or separately in another location (see
the figure below).
D
C
DIMENSIONS (m) A
B
C
>0,5 >5 ≥2,1 >1
Important: For correct distribution of the steam, observe
the distance shown in the figure above.
12
1
2
6
7
8
Y
B
Fig. 3.b
CAREL linear distributors
DP***D30R0
DP***D40R0
30 (1.18")
40 (1.57")
10 (0.4")
10 (0.4")
68 (2.7")
89 (3.5")
45 (1.8")
60 (2.4")
77 (3.0")
99 (3.9")
Tab. 3.bTab. 3.a
G
D
DIMENSIONS (m) E
F
>0,5 >5 >1
Fig. 3.c
di
G

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents