Important: before proceeding, disconnect the humidifier from
the power supply.
Models UE005 to UE015
1
4
5

Water connections:

1. install a manual valve upstream of the installation (to be able to cut off the water supply);
2. connect the humidifier to the water supply. On models UE005 to UE0015, use a hose with 3/4''G fittings (see par. 11.2 "Technical specifications" ,
compatible CAREL hose: code FWH3415000). On models UE025 to UE065 connect the hose with the non-return valve supplied (code FWHDCV0000) to
prevent the water inside the humidifier from coming into contact with the mains water;
3. install a mechanical filter to trap any solid impurities (to be connected downstream of the tap);
4 connect a section of non-conductive pipe or hose for draining (resistant to temperatures of 100 °C (212 °F) and with a minimum inside diameter of 40
mm/1.6");
5 prepare a funnel to interrupt continuity in the drain line;
6 connect a drain trap to prevent the return of bad odours (minimum inside diameter 40 mm/1.6");
7 in models UE025 to UE0065: connect a drain hose ( minimum inside diameter 15 mm ( 0.59" )) from the bottom tank of the humidifier (this can run into
the drain funnel).
Important : when installation is completed, flush the supply hose for around 30 minutes by piping water directly into the drain, without sending
it into the humidifier. This will eliminate any scale or processing residues that may block the drain pump and cause foam when boiling.
Fittings provided for the water connections:
Models UE005 to UE015
B
A
"UE BASIC" +08C0042EZ - rel. 1.0 - 16.10.2017
2. WATER CONNECTIONS
2
3
6
Models UE025 to UE065
A
B
C
Fig. 2.b
Models UE025 to UE065
4
2
1
3
7
4
5
6
Fig. 2.a
Key:
A.
supply water inlet
B.
drain water outlet
C.
bottom tank drain water outlet (models UE025 to
UE065 only)