OPERATION & MAINTENANCE MANUAL
2.4.1.7 IN-TANK LEAK TEST – DETAILED RESULTS
Log
Inventory
deLivery
SALES
tHEFtS
Orders
Water
tank Leak
Leak Hist
LIne Leak
ALArMS
Events
return
tank Leak In-Tank Leak Test: detailed In-Tank Leak Test results showing the average change at the end of each
hour. The settings for In-Tank Leak Testing are found both in the Tank Leak submenu of the
Configuration menu and in the Leak Test menu.
Record Storage Capacity: 12, 1 per Tank Channel
TMS Configuration Prerequisites:
Leak Test menu: Scheduling, duration, and other test controls.
Configuration menu, Tank Leak submenu: Test configuration including Test Type and Leak Rate.
Group ID: Tank Channel Number.
Record Identification Data:
mm-dd
Date (Month-Day): Date the In-Tank Leak Test completed.
Note: an empty record will show 00-00.
Starttime Start Time: Time the In-Tank Leak Test began.
Note: time stored in 24 hr. format
Examples 12'00 = 12 Noon
End time
End Time: Time the In-Tank Leak Test completed.
Note: time stored in 24 hr. format
tank Name Tank Name: As Assigned in the Configuration menu, Tank submenu.
Prod type Product Type: As Assigned in the Configuration menu, Tank submenu.
tank id
Tank ID Number: As Assigned in the Configuration menu, Tank submenu.
Captured Data:
Net Begin Beginning Net Volume: Total Net Volume at the Beginning of the In-Tank Leak Test.
Net End
Ending Net Volume: Total Net Volume at the End of the In-Tank Leak Test.
Beg temp
Beginning Temperature: Average Product Temperature at the Start of the In-Tank Leak Test.
End temp
Ending Temperature: Average Product Temperature at the End of the In-Tank Leak Test.
LeakLimit Leak Limit: Leak Threshold for determining Pass/Fail. See Configuration menu, Tank Leak
submenu, Leak Limit setting.
Rate GPH
Leak Rate GPH/LPH: Observed average hourly gain/loss of Gross Volume.
ResULt
Test Result: PASS or FAIL. In-Tank Leak Test result.
Rate hr1
Leak Rate Hour-1: Observed average gain/loss of Gross Volume at the end of the first hour.
Rate hr2-8 Leak Rate Hour-2-8: same as above averaging in each additional hour 2-8 inclusive.
Exit Tank Leak submenu:
Return
Return: Press EDIT (TEST) to exit Tank Leak submenu.
Note: Press STEP (MODE) to return to top of Tank Leak submenu showing mm-dd
(Month-Day)
TMS Operations and Maintenance Manual.docx
Inventory
Deliveries
Bulk Sales
Thefts
Product Reordering Report
Bottom Water Removal
In-Tank Leak Test – Detailed Results
In-Tank Leak Test – History
LS300 Line Leak Test
Alarms
Events
Return
23'59 = 11:59 PM
PAGE 23
TMS2000/3000
00'00 = Midnight
February 12, 2018
Need help?
Do you have a question about the TMS2000 and is the answer not in the manual?