Figure 65
shows a cabling diagram for implementing a start function on the first digital
input and a stop function on the second digital input.
24 Vdc
external
supply
-
+
Remark:
(a)
Left hand terminal block when looking from rear, counting from top to bottom
Figure 65: Cabling diagram for implementing start on digital input 1 and stop
-
The second approach is to use one digital input for both the start function and
the stop function. This leaves the other digital input available for the
implementation of other functions.
Table 35
shows the PQF-Manager setup for the input considered and the resulting effect
when applying voltage to this input.
Table 35: Filter behavior as a function of the PQF-Manager settings for local start/stop and
PQF-Manager setup for
digital input
Edge ON/OFF
Remark: Vlow = 0 Vdc, Vhigh = 15-24 Vdc
Refer to
Section 7.9.1.4
the function required.
The electrical requirements of the digital inputs are as discussed in
66
shows a cabling diagram for implementing a start function and a stop function on
the first digital input.
86 Electrical design and installation ç Manual Power Quality Filter PQFM
External
External
start
stop
push
push
on digital input 2
using 1 digital input
Vlow applied to digital
input
No effect
for guidelines on how to set up the digital inputs according to
PQF-Manager
1
(a)
Digital input 1 (15-24Vdc)
2
(a)
3
(a)
4
(a)
Digital input 2 (15-24Vdc)
Vhigh applied to digital input
Filter starts on first rising edge, stops
on second rising edge, etc
Section 4.5. Figure