57). Any digital input can be configured to act as the deciding factor for switching
between the main and auxiliary settings. Moreover, both normal and inverse logic can be
used to drive the digital inputs.
Note that in a multi-unit filter system in which more than one master system is present,
the digital inputs of all masters have to be set up and cabled in the same way to obtain
full redundancy.
The electrical requirements of the digital inputs are as discussed in
Figure 64
gives an example of how to implement the main/auxiliary control switching
functionality on Digital Input 2. It is assumed that normal control logic is used.
Figure 64: Example of how to cable the 2
When implementing the function described above, please note that according to the
setup done with the PQF-Manager for the input considered, the filter may behave
differently.
Table 33
WARNING: If a function is assigned to a digital input, the same function must never be
assigned to the other digital input. Otherwise the filter may behave erratically.
Table 33: Filter behavior as a function of the PQF-Manager settings for
PQF-Manager setup for
digital input
Activ. Main
Activ. Aux.
Remark: Vlow = 0 Vdc, Vhigh = 15-24 Vdc
84 Electrical design and installation ç Manual Power Quality Filter PQFM
24 Vdc
external
supply
-
+
External switch for
switching between main
and auxiliary filter settings
Remark:
(a)
Left hand terminal block when looking from rear, counting from top to bottom
control switching functionality
shows the filter behavior as a function of the PQF-Manager settings.
main/auxiliary switching
Vlow applied to digital
input
Auxiliary settings are
used
Main settings are used
nd
digital input of the PQF-Manager for main/auxiliary
Vhigh applied to digital input
Main settings are used
Auxiliary settings are used
Chapter
PQF-Manager
(a)
3
Digital input 2
(a)
(15-24Vdc)
4
12.