The 'Active Warnings' Menu; The 'Number Of Errors' Menu - ABB PQFM Instruction Manual

Power quality filter
Table of Contents

Advertisement

A fault is considered critical if after occurrence, it cannot be successfully
automatically cleared by the system within a reasonable time. The time frame
considered depends on the error type.
In practice the word 'Critical' will appear in the 'Event logging' window if the
system has detected a critical error. The user can then backtrack in the logging
window to see which errors were already present in the previous events, to know
which is/are the critical error(s).

7.10.4 The 'Active warnings' menu

The 'Active warnings' menu is constantly updated by the system. It shows at any time
the warning conditions set up by the customer that are met. For more information on
setting up the programmable warnings, refer to
warning in the detailed
Table 55
shows an overview of the warning messages that will be displayed and the
corresponding warning condition.
For multi-master filters, this data can be obtained for each individual unit.
Table 55: Warning messages that can be displayed by the PQF-Manager and corresponding
Warning condition
Supply voltage (RMS) higher than preset value
Supply voltage (RMS) lower than preset value
Supply voltage imbalance higher than preset
value
PQF IGBT temperature higher than preset value
PQF control board temperature higher than
preset value

7.10.5 The 'Number of errors' menu

146 The PQF-Manager user interface ç Manual Power Quality Filter PQFM
manuals.
warning conditions
Section 7.9.1.4
and the list of possible
Warning message displayed
Over voltage RMS
Under voltage RMS
Unbalanced supply
IGBT temperature
Ctrl over temperature