ABB PQFM Instruction Manual page 162

Power quality filter
Table of Contents

Advertisement

Table 57: Possible filter unit addresses and corresponding DIP switch settings (facing the board
Filter address
1
2
3
4
5
6
7
8
Notes:
-
Do not use other settings than the ones mentioned in the table.
-
It is recommended to assign increasing addresses starting from the main master
at the left and moving right.
-
Assigning the same address to different filter units in one filter system will lead
to the filter not being able to start up and go in error (Bad Ratings).
When a filter consists of more than one unit, attention has to be paid to the proper
termination of the communication bus between the different units. This communication
bus is depicted in
From previous unit (if present)
Control board in the 'previous' unit
In order to terminate the bus correctly, the fourth switch (counting from bottom to top)
from DIP switch 22 (Cf.
-
Left: For the first unit in a filter system (single unit filter or first physical unit of a
multi-unit filter).
-
Left: For the last physical unit of a multi-unit filter.
-
Right: For all the other units.
162 The PQF-Manager user interface ç Manual Power Quality Filter PQFM
with ABB logo at the left hand side), counting bottom to top.
DIP switch 1
setting (ID0)
Right
Left
Right
Left
Right
Left
Right
Left
Figure 90
by the black lines interconnecting the different units.
Figure 90: Communication bus between different filter units
Figure
89) has to be set as follows:
DIP switch 3 setting (ID2)
DIP switch 2
setting (ID1)
Right
Right
Right
Right
Left
Right
Left
Right
Right
Left
Right
Left
Left
Left
Left
Left
Control board in the 'next'
To next unit
(if present)