Fault message
DC overvoltage (HW)
DC undervoltage (SW)
Ground fault
IGBT check cooling
Cause
The DC hardware
overvoltage protection
has been triggered.
The DC software
undervoltage protection
has been triggered.
A ground fault has been
detected.
The software IGBT
temperature protection
has been triggered.
Manual Power Quality Filter PQFM ç Troubleshooting guide 213
What to do
- Check the connection between the
DC voltage measurement connectors
(P6-5 and P6-7) and the DC
capacitors.
- Check flat cable connections between
the Control Board and the IGBT
module.
- Analyze network voltage stability
(amplitude and phase).
- Disable reactive power compensation
and balancing options to see if the
problem persists.
- Deselect the high frequency
components to free DC bus resources
and to see if the problem persists.
- Check the connection between the
DC voltage measurement connectors
(P6-5 and P6-7) and the DC
capacitors.
- Check flat cable connections between
the Control Board and the IGBT
module.
- Analyze network voltage stability
(amplitude and phase).
- Disable reactive power compensation
and balancing options to see if the
problem persists.
- Check the main contactor and its
control signal.
Check the equipment for possible
connections to earth.
- Check the cooling of the filter system
(fans and air flow, heatsink).
- Check the cooling of the location
where the filter is installed (air
conditioning system etc.)
- Ensure that the correct derating
factor is applied noting the ambient
temperature and altitude.