Dc Capacitor Change; Dc Capacitor Reforming (V1 Range Only, 208 V £ Ue £ 480 V) - ABB PQFM Instruction Manual

Power quality filter
Table of Contents

Advertisement

The components description is given in
Item
Description
1
X23 terminal block
2
Fan capacitor
3
IGBT cooling fan
Apart from the main IGBT cooling fan, the filter may incorporate a small air blower in the
filter door or at the cubicle top. This fan has an operating life of about 35,000 hours. In
order to replace this fan switch off the power to the cubicle, remove the electrical
connections and subsequently remove the fan physically. Proceed in reverse order for
adding a new fan.

10.5 DC capacitor change

Active filters of V1 range (208 V ≤ Ue ≤480 V) have a DC link that contains electrolytic DC
capacitors. Active filters of V2 range (480 V < Ue ≤690 V, CE version, 480 V < Ue ≤600 V,
cULus version) have a DC link that contains film capacitors. Their service lifetime is 8
years (208 V ≤ Ue ≤ 480 V) or 10 years (480 V < Ue ≤ 690 V, CE version, 480 V < Ue ≤ 600
V, cULus version) depending on filter loading and ambient temperature. Announced
service lifetime assumes that the filter is operating under ABB approved conditions (Cf.
Chapter
12).
It is not possible to predict a capacitor failure. Contact your ABB service provider if
capacitor failure is suspected. Replacement kits are available from ABB. Do not use other
than ABB-specified spare parts.
10.6DC capacitor reforming (V1 range only, 208 V £ Ue £ 480 V)
If the filter has been non-operational for more than one year, the DC capacitors must be
reformed (re-aged) before use. Without reforming, the DC capacitors may be damaged
at start-up.
198 Maintenance instructions ç Manual Power Quality Filter PQFM
2
Figure 104: Overview of IGBT cooling fan related items
Table 60: IGBT cooling fan related items description
Table
60.
1
3

Advertisement

Table of Contents
loading

Table of Contents