Salus FC600 Instruction Manual page 54

Fan coil thermostat
Hide thumbs Also See for FC600:
Table of Contents

Advertisement

Parameter
Type of setting
number
d 17
Set the Span
control for heating
mode respectively
d 18
Set the Span
control for cooling
mode respectively
d19
Set the minimum
turn off time for
heating mode
respectively
d20
Set the minimum
turn off time for
cooling mode
respectively
d21
TPI heat control CPH
d22
TPI cool control CPH
d23
Dead zone Comfort
mode (4 pipe only)
d 24
Heat/cool
changeover cooling
switch-point Heat/
cool changeover
cooling switch-
point Heat/cool
changeover cooling
switch-point
d25
Heat/cool
changeover heating
switch-point
d 26
S1 - COM input
position
d 27
S2 - COM input
position
d28
Service filter
d29
Protection heating
set point
54
Fan Coil FC600 Instruction Manual
Description
The range of span is 1 to 20 (0.1K to 2.0K)
Mean: 1=0.1K...20=2.0K
The range of span is 1 to 20 (0.1K to 2.0K)
Mean: 1=0.1K...20=2.0K
10 to 300 seconds
10 to 300 seconds
3 – 12 on/off cycle per hour
3 – 12 on/off cycle per hour
1.0 to 5.0K
The value of this parameter is used by the pipe
temperature sensor to switch to Heating mode. When
the temperature acquired by the sensor is above this
parameter's value, the thermostat will switch to heating
mode.
The value of this parameter is used by the pipe
temperature sensor to switch to Cooling mode. When
the temperature acquired by the sensor is below this
parameter's value, the thermostat will switch to cooling
mode.
0 = Normally open
1 = Normally close
0 = Normally open
1 = Normally close
The 'clean fan filter reminder' function counts the fan
operating hours. Is OFF or from 0.1 to 9.9 (9.9 means
9900hrs = 9.9*100)
OFF or from 5⁰C to 40⁰C (d29 value can not higher than
d30)
Default
Values
0.3K(This
parameter is
ignored if
TPI control is
selected)
0.5K (This
parameter is
ignored if
TPI control is
selected)
10
10
6
3
2.0
10⁰C
30⁰C
0
0
Off
8