P0852 - Ethercat Link Status - WEG SCA06 User Manual

Ethercat
Hide thumbs Also See for SCA06:
Table of Contents

Advertisement

Value
0 = Inactive
1 = Access error
2 = Watchdog error
3 = Offline
4 = Online
P0852 – ETHERCAT LINK STATUS
Range:
Properties:
Description:
Parameter that provides information about the state of communication for each available Ethernet port on the module.
Uses a binary field, where each bit represents a different information:
Bit
15
14
Function
Bit
Bit 0...3
Bit 4
Link 1 OK
Bit 5
Link 2 OK
Bit 6...7
Bit 8
Port 1: Loop active
Bit 9
Port 1: Communication
Established
Bit 10
Port 2: Loop active
Bit 11
Port 2: Communication
Established
Bit 12...15
Table 5.2: Indications of parameter P0851
Interface not installed or not recognized by the device.
Error during the initialization procedure of EtherCAT module.
Error in the watchdog mechanism between accessory and device, responsible by
checking if data update between both are running successfully.
EtherCAT module running properly, but there is no cyclic data exchange with the network
master.
EtherCAT module running properly, with cyclic data exchange with the network master.
0000h ... FFFFh
ro, ecat
13
12
11
10
Table 5.3: P0852 bits indication
Reserved.
0: Port 1: No link.
1: Port 1: Link active.
0: Port 2: No link.
1: Port 2: Link active.
Reserved.
0: Port 1: No loop.
1: Data loop active at port 1, to return response to the master.
0: No communication at port 1.
1: Communication established at port 1.
0: Port 2: No loop.
1: Data loop active at port 2, to return response to the master.
0: No communication at port 2.
1: Communication established at port 2.
Reserved.
Description
9
8
7
6
Value/Description
Parameterization
Default: -
5
4
3
2
1
0
SCA06 | 15