P0800 - Ethernet Module Identification; P0801 - Ethernet Communication Status - WEG SCA06 User Manual

Ethernet communication module
Hide thumbs Also See for SCA06:
Table of Contents

Advertisement

Option
0 = Show Alarm
1 = Generate Fault
2 = Run STOP function
3 = Disable drive
The following events are considered communication errors:
Ethernet communication:
Alarm A0147/Fault F0047: communication error with Ethernet master.
Alarm A0148/Fault F0048: Ethernet interface error.
P0800 – ETHERNET MODULE IDENTIFICATION
Range:
Properties:
Description:
It allows identifying the Ethernet module type connected to the equipment.
Indication
0 = Not Identified
1 = Modbus TCP
2 = EtherNet/IP
3 = PROFINET IO
P0801 – ETHERNET COMMUNICATION STATUS
Range:
Properties:
Description:
It allows identifying the Ethernet communication status.
Table 5.1: Option for parameter P0662
If a communication error occurs, only indicates alarm in the keypad. If the communica-
tion is reestablished, the alarm indication is automatically removed.
Instead of an alarm, a communication error causes a fault in the equipment, and it is
necessary to reset the failure to return to normal operation.
It will indicate an alarm along with the execution of the STOP command. To start oper-
ation again, it is necessary to run the fault reset or disable the drive.
It will indicate an alarm along with the execution of the disable command.
0 = Not Identified
1 = Modbus TCP
2 = EtherNet/IP
3 = PROFINET IO
RO, ETH
Table 5.2: P0800 indications
Module not connected / not identified.
Ethernet module for communication with Modbus TCP protocol.
Ethernet module for communication with EtherNet/IP protocol.
Ethernet module for communication with PROFINET IO protocol.
0 = Setup
1 = Init
2 = Wait Comm
3 = Idle
4 = Data Active
5 = Error
6 = Reserved
7 = Exception
8 = Access Error
RO, ETH
Description
Description
Parameterization
Default: -
Default: -
SCA06 | 15