Comissioning guide

Advertisement

Program setup - fan
Controller setup
Press anywhere on the display and then press the OPE-
RATION icon.
Operation settings menu:
Use the + and - buttons together with OK and the Return
key to navigate the menu system.
- Confirm that burner is set to OFF.
Fan menu:
Enter the FAN menu, a passcode is required which is
2233. The fan values are set up during operation with
a flue analyzer according to the installation manual. We
can however recommend the following values to get the
boiler operating enough to be able to measure with a flue
analyzer:
20kW
Fan burner
55%
Flue boiler
65%
The "Fan burner low" parameter is set to ON if you which
to have the low power output mode activated. We recom-
mend to have it activated on a Komplett III Light which di-
rect feeds any heating circuit without a accumulator tank.
Please leave the menu by pressing the Return key repea-
tedly until the home screen appears.
6
Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se
25kW
35kW
65%
55%
75%
90%
Operation settings
Burner
Fan
Feeder settings
Temperature set
Information
Service
Installation
VER: 3.0
Fan
Fan burner
Flue boiler
Fan burner low
Fan alarm
Fan alarm
Off
65%
75%
Off
Tacho
5s